(4)Requirements for beds and signs
Each section or partition of patient ward or cabin shall have clear signs and labels.Area for men and women shall be separated.Each section of ward shall not have more than 42 beds.Each partition or section should have two evacuation or emergency exit.The distance between the evacuation exit and patient section should not exceed 30 meters(m).Fire evacuation passages should be identified between the areas.The width of the fire evacuation passages between zones should not be narrower than 4 meters in high spaces.The ground evacuation signs on the ground or floor shall be indicated to the sections.Partition material for cabins or beds should be fireproof,easy to clean surface,with the height lower than 1.8meters.The beds should be arranged at a suitable distance to facilitate care and treatment.The clear distance between two paralleled beds should not be narrower than 1.2 meters,and a bedside table should be provided.The clear distance of the aisle between double beds(bed end)should not be narrower than 1.4 meters.Width of the aisle between single bed and the wall shall not be less than 1.1 meters.(https://www.daowen.com)