(2)Water supply system

更新于 2026年11月22日 版权声明
(2)Water supply system

Water supply system should be water tank water supply with pump and with cutoff switch,and with sterilization device.If condition not allowed,risk level of potential backflow pollution should be evaluated according to the provisions of the Standard for Building Design of Water Supply and Drainage(GB 50015—2019).Following requirements shall be met:

1)When the risk of backflow pollution is low and the water supply pressure meets the requirements,the water supply system should use a pressure-reducing backflow preventer to prevent backflow contamination.

2)When the risk is high,the water supply should have cutoff switch.

3)The water supply system in toilet and bathroom/shower area should have airstop or backflow prevention device.Clean water supply shall have mechanism to prevent contamination with siphon back flow or back pressure backflow.

4)Water drainage and collection from temporary mobile toilet shall be separated from those in shower area.

5)Water drainage should be non-shrink,with dustproof seal.The vent on the drain pipe must not be connected to the exhaust duct of the air conditioning ventilation system.

6)Vehicle washing and disinfection wastewater should be drained to the sewage system,and drainage outlet with water seal.The depth of the water seal must not be less than 5 cm.It is strictly prohibited to use movable mechanical flaps to replace the water seal.(https://www.daowen.com)

7)Do not use plugs in sink.

8)The drainage system shall adopt technical measures to prevent the damage of the water seal.

9)The drainage of the shower area should be collected in a sealed manner and let into the sewage system after disinfection.

10)The hot water in shower area should be from centralized supply system,and an airsource heat pump water heater should be used.Electric water heater shall be equipped with safety device.

11)Each ward should be supplied with a separate drinking water system,and the water supply should provide drinking water and hot water.The quality of water should comply with the Sanitary Standards for Drinking Water(GB5749—2006).Bottled water dispensers can also be used.

12)Water from the shower area should be drained into the sewage system after disinfection.