6.Electrical and intelligent management requirements

(1)After conversion or reconstruction,electric power supply shall meet the power demand of the load,and the additional power lines should meet the required protection sensitivity.

(2)The distribution electric box and control box shall be located outside the dirty area,and should be placed in a special room when conditions permit.

(3)The ventilation equipment control box should be packaged in a complete set of products and be controlled centrally by the nurse station or duty room.

(4)When conditions permit,each bed should be equipped with 1-2 220V,10A single outlets and lamps.If conditions is not available,multiple sets of single-outlet electrical box in large extension,can be used for patients to charge cell phones.When a electric blanketis needed,the electric power supply should be equipped with a separate power circuit,with centralized and separate timing control to reduce the risk of fire.

(5)When conditions permit,more lighting fixtures could be installed on the surrounding wall of the large room,or free-standing floor lights on the ground,with opaque cover or indirect lighting to reduce the glare from the ceiling of the building.

(6)Lighting and socket circuits should use 30 mA residual current protectors.

(7)Wireless network access should be provided to ensure full coverage of 4G or 5G networks.Where conditions permit,wireless APs should be added to achieve full Wi-Fi coverage.

(8)The additional floor lighting,power line outlets and current lines on the ground shall be laid with metal pipes or pipes with slots to avoid the passage or hallway for people and packages.(https://www.daowen.com)

(9)In medical places and other places that need to be sterilized,ultraviolet(UV)germicidal lamps or air sterilizer sockets need to be installed.UV lamps should use special switches with clear signs.It should not be parallel or juxtaposed with regular lamp switches.If the place where people are gathered needs ultraviolet germicidal lamps,indirect lamps or lamps with adjustable angles should be used.

(10)The auxiliary electric equipment shall be provided in the medical equipment room,shower room or bathroom.

(11)A one-touch alarm button,with access to the hospital security system,shall be set in the nurse station or duty room.

(12)Patient ward areas and nurse stations could be covered by video surveillance.

(13)If the floor wiring cannot be implemented during reconstruction of electricity and intelligent system,wireless solution shall be considered.

(14)After conversion or reconstruction,information management system could be shared according to the requirements needed.