Ventilation requirements
(1)Contaminated dirty area and semi-dirty area shall mainly use natural air or mechanical ventilation.Air conditioning system should turn on air purifying and disinfection apparatus.Clean area with small space can use natural air or mechanical ventilation.
(2)If possible,the air conditioning unit shall be equipped with a clean air conditioning system with efficient air filter or air purifier; ultraviolet disinfection lamp can be installed near the return air filter.
(3)Medical area and patient ward area shall be ventilated through temporary air intake and exhaust,air flow from the medical area toward patient ward area in a reasonable way.
(4)When the existing air conditioners and ventilation systems can be used,DC transmission and exhaust air duct systems shall be considered.With air conditioning with return air valve turned-off,the new air valve can be fully opened.Fresh air into the exhaust volume should be larger than supply air volume.When the exhaust air volume is not enough,the smoke fan can be turned on.Medium to high efficiency filter can be installed at the entrance of the exhaust fan.If the original air conditioner and exhaust system cannot be used or there is no ventilation system,a ventilation system shall be added.When a temporary exhaust system is added,it is advisable to select those with appropriate air volume and pressure,the height less than 2 meters,and with protective measures.The ventilation system requires 24 hour uninterrupted operation.
(5)Exhaust volume should be not less than 150 m3/h per person by design.
(6)After“First donning room-second donning room-buffer room”,medical staff can move from clean area to the ward,the contaminated area.In first donning room,air supply shall be set to be>30 times/h,adjacent compartments with D300 short ventilation pipe,air flowfrom clean area to ward area.The exit passage used by medical personnel shall be set to be >30 times/h,and adjacent compartment with a D300 short ventilation pipe,and the air flows from the clean area to the contaminated area.(https://www.daowen.com)
(7)In each ward region,air filter with disinfection function shall be provided,and certain oil heater if necessary.
(8)Emergency dry toilets should be used in the patient ward area.Exhaust fans should be added to the toilets in the ward and in the medical staff area to meet the air change frequency of 12 times/h.Filter with high efficiency should be installed at the inlet of the exhaust fan.
(9)The location of the fan and exhaust system should be selected according to the actual situation.It should be ensured that the fresh air is taken from the outside.The fresh air outlet and the surrounding environment must be clean to ensure that the fresh air is clean.The outdoor exhaust should be installed high,and the horizontal distance from any air inlet should be>20 meters,and the vertical distance should be>6 meters.
(10)Ventilator alarm and signal shall be monitored in real time,to ensure the normal operation of the fan.The air filter system,exhaust air volume,and air supply,need to be checked and to be replaced timely if clogging occurs.
(11)Self-protection is required to replace of exhaust HEPA filter.Only designated and trained personnel can remove,disinfect,and dispose exhaust filter in the secure container,together with other medical waste.